40
Remove multiway
connector from board
position ST16. Test
resistance across pins
16 and 17 ( yellow
wire). Is it between 1
kOhm and 30 kOhm?
Test resistance across
contacts 12 and 13
(red wire). Is it
between 1 kOhm and
30 kOhm?
Is there continuity
from individual pins
16 and 17 to DHW
sensor?
Check or replace
DHW sensor.
Is there continuity
from individual
contacts 12 and 13 to
CH sensor?
Repair or replace
harness.
Repair or replace
harness.
Is the multiway
connector at board
position ST16 pushed
fully home on to the
board?
Push fully home
No
No
No
No
No
Yes
Yes
Yes
Check the DHW
sensor. Is it correctly
fitted onto the pipe
with heat conductive
paste between the
pipe and sensor?
Yes
No
Re-fix sensor onto pipe
TEST E
Check or replace
CH sensor.
Test resistance across
contacts 14 and 15
(green wire).
Is it open circuit?
Turn off electrical
supply.
Remove fan connector
from board position
ST1.
Test resistance across
contacts to black &
white cables.
Is it between 75 and
175 ohms?
Check/repair fan
harness or repalce fan.
Air pressure switch
is shorting.
Check tubes for
blockage or replace
switch.
No
No
Yes
Yes
Yes
Test resistance across
contacts to black &
red cables. Is it
between 30 and 90
ohms?
Yes
Yes
No
5
3. Technical Data
MAXIMUM AVAILABLE PUMP HEAD
BOILER OUTPUT HEAD MIN. FLOW RATE
kW Metres L/min. °C
8 4.5 10.4 11
23.5 2.2 18.3 18
27.5 2.0 18.3 21
Table 3
MECHANICAL SPECIFICATIONS 24i 28i
CENTRAL HEATING FLOW - COMPRESSION 22mm 22mm
RETURN - COMPRESSION 22mm 22mm
COLD WATER INLET - COMPRESSION 15mm 15mm
DOMESTIC WATER FLOW - COMPRESSION 15mm 15mm
GAS INLET Rp
3
4 Rp
3
4
RELIEF VALVE DISCHARGE 15mm 15mm
CASING HEIGHT 600mm 600mm
CASING WIDTH 400mm 440mm
CASING DEPTH 325mm 325mm
WEIGHT - LIFT 22kg 23.5kg
WEIGHT - PACKAGED 37kg 40kg
WEIGHT - DRY 34.7kg 37.5kg
Table 4
FLUE DETAILS
HORIZONTAL FLUE
WALL HOLE DIAMETER EXTERNAL FIX mm 110
INTERNAL FIX mm 130
STANDARD FLUE MINIMUM LENGTH mm 275/*425
MAXIMUM LENGTH mm 725
EXTENDED FLUE MAXIMUM LENGTH mm 3000
FLUE ASSEMBLY DIAMETER mm 100
VERTICAL FLUE
VERTICAL DUCT MAXIMUM LENGTH mm 3000
TERMINAL ASSEMBLY mm 1100
Table 2.
FLOW/RETURN
DIFFERENTIAL
* NOTE : Minimum uncut length
NOMINAL BOILER RATINGS (10 Minutes After Lighting)
BOILER ADJUSTED FOR G20 (Natural Gas)
OUTPUT INPUT (Net) GAS RATE
kW kW m bar. m
3
/h
8.0 9.5 1.2 1.00
27.5 30.0 14.7 3.17
BOILER ADJUSTED FOR G31 (Propane)
8.0 9.5 3.4 0.39
27.5 30.0 35.3 1.23
Table 1. 28i
BURNER
PRESSURE
NOMINAL BOILER RATINGS (10 Minutes After Lighting)
BOILER ADJUSTED FOR G20 (Natural Gas)
OUTPUT INPUT (Net) GAS RATE
kW kW m bar. m
3
/h
7.5 9.5 1.4 1.00
23.5 25.9 13.6 2.74
BOILER ADJUSTED FOR G31 (Propane)
7.5 9.5 4.6 0.39
23.5 25.9 35.0 1.06
Table 1. 24i
BURNER
PRESSURE
Natural Gas: Net Input = Gross Input x 0.901 LPG (Propane): Net Input = Gross Input x 0.921