39
Remove combustion
chamber cover.
Is the sense electrode
and lead in good
condition and is gap
correct?
Replace flame sensor
or wiring.
No
No
Remove multiway
connector from board
position ST16.
Is there continuity
from pin 10 (white
wire) to flame sensor?
Yes
Yes
Yes
Replace control board.
NOTE: It is not
possible to reliably
check the cross-light
performance of the
burner or the
efficiency of the
gas/water heat
exchanger.
If there is still a
problem, investigate
flue problems or
replace burner or
injector or heat
exchanger.
Check the flashing
fault signal occur at
the start of a demand.
Check flashing occurs
at the end of a
demand.
Gas valve leak is
detected.
No
Yes
Check flashing occurs during
a demand.
Pump could be partially
blocked.
Clean pump & flush system.
Re-fix sensor to pipe.
No
Turn off boiler. Remove
inner casing cover and
check position of
primary sensor (on
heat exchanger in
front of overheat
thermostat).
Is it correctly fixed to
pipe?
Yes
PERFORMANCE SPECIFICATIONS 24i 28i
PRIMARY WATER CAPACITY litres 3 3
IP RATING (WHOLE OF BOILER) IP 20 IP 20
MAXIMUM MAINS INLET PRESSURE bar 10 10
MINIMUM MAINS INLET PRESSURE (WORKING) FOR MAXIMUM FLOW bar 0.9 0.9
MINIMUM MAINS INLET PRESSURE (WORKING) FOR OPERATION bar 0.1 0.1
DOMESTIC HOT WATER TEMPERATURE RANGE °C 55 55
MAXIMUM CENTRAL HEATING FLOW TEMPERATURE °C 82 (nom) 82 (nom)
MAXIMUM CENTRAL HEATING SYSTEM SET PRESSURE bar 2.5 2.5
MINIMUM CENTRAL HEATING SYSTEM PRESSURE bar 0.5 0.5
OUTPUT TO CENTRAL HEATING & DHW kw NATURAL GAS (G20) 23.5 27.5
LPG - PROPANE (G31) 23.5 27.5
DOMESTIC HOT WATER SPECIFIC RATE - 30°C RISE l/min 11.2 13.1
MAXIMUM DOMESTIC HOT WATER FLOW RATE - 40°C RISE l/min 8.4 9.8
FLUE GAS MASS FLOW RATE 15.2 17.8
FLUE GAS TEMPERATURE °C 150 150
NOx CLASSIFICATION FOR BOTH 24i & 28i Class 2
SEDBUK NUMBER NG 78.0 78.9
SEDBUK NUMBER LPG 80.4 82.1
SEDBUK BAND* D D
6
GAS SUPPLY SYSTEM - BASED ON NG (G20)
TOTAL LENGTH OF GAS SUPPLY PIPE (COPPER) metres
3 6 9 12
GAS DISCHARGE RATE - PRESSURE DROP 1 mbar. — m
3
/h PIPE DIAMETER mm
8.7 5.8 4.6 3.9 22
18.0 12.0 9.4 8.0 28
Table 7
CLEARANCES (mm)
INSTALLATION SERVICE UNVENTILATED COMPARTMENT
*ABOVE FLUE ELBOW 30 30 30
BENEATH THE APPLIANCE 200 200 200
IN FRONT OF APPLIANCE 600 600 25**
RIGHT/LEFT HAND SIDE 10 10 25
Table 8
SYSTEM CAPACITY
TOTAL SYSTEM VOLUME litres
INITIAL INITIAL CHARGE PRESSURE bar
PRESSURE bar 0.5 1.0 1.5
1.0 57 75 N/A
1.5 31 42 52
Table 9
Refer to Section 6.
* If vertical flue then 200mm above top of boiler.
** Front clearance is to a removable panel (eg. door).
DOMESTIC HOT WATER TEMPERATURE RISE
DISCHARGE RATE l/min 7 8 9 10
TEMPERATURE RISE °C 24i 48 42 37 34
TEMPERATURE RISE °C 28i 56 49 44 39
Table 6
Table 5
* The value is used in the UK Government Standard Assessment Procedure [SAP] for the energy rating of dwellings. The test data from
which it has been calculated have been certified by the GASTEC notified body.